A properly obliterated circuit breaker that gave someone a burn when it failed in an industrial environment.

My apologies to those who don't like the auto dubbed speech when it is applied by default. If the video is viewed on YouTube you can manually select your preferred language.

I'm giving it a test to see if it makes my videos available to non-English speaking countries. (Especially for those who speak Spanish and Urdu.)

https://youtu.be/DdB2i-Yb6po

Files

Arc flash breaker failure - let's open it

One of the most violent electrical failures is where an arc flash occurs. This is where an initial arc situation creates a conductive mix of ionised air and vaporized metal that can continue to sustain an arc, and also carry it across onto adjacent metalwork that could be grounded or a different phase. That can result in an electrical explosion where it instantaneously bridges multiple phases in the vicinity, with the risk that the affected metalwork may be high current busbars that can literally supply megawatts or gigawatts of power instantly. Arc flash poses a high burn risk - with the added complexity of the arc being metal laden, which makes the burns much worse. The plasma is also carrying current and when it engulfs a worker, some of that current can pass through them, posing an electrocution risk. The carbon tracking issue can be very difficult to pin down if it is not to ground, and when it blows itself clear. If it was to ground then an insulation test would generally help pinpoint the area of the fault. But when it's not to ground then you have loads across the conductors that defeat the insulation test and make troubleshooting more complex. Especially so when a cable fails in a long run and is underground or in inaccessible containment as happened here. In some instances the time between the tracking causing flashover and blowing the fault clear can be so long that it becomes normal just to reset the breaker or change a fuse. Ultimately the fault may get more frequent until it does persist and becomes easier to locate. Note that blowing faults clear shouldn't be considered a normal thing. When it starts involving stupidity like uprating or bridging protective devices completely, then there is a serious risk of cable damage and fire when a fault turns into a solid short circuit. Normally a circuit breaker like this will quench a high current arc by guiding it up conductive plates into a series of fins that effectively break the arc. But over time, if a circuit breaker is exposed to too many high current faults, it can create a progressive build up of carbon and metallisation inside that can lead to an issue like this, where the arc chose a different route to the normal quenching system and was sustained with explosive results. It's interesting that the mechanism interfacing ports between the trip mechanisms of adjacent breakers are close enough to live internal metalwork, that a high current arc flash in one looks like it did spread into the breaker either side. If you're in a situation where you believe you may be closing a breaker into a fault, I recommend at least wearing gloves that are suited to protecting you from ejected flame, and preferably eye protection too. With very high power equipment it really requires proper full body protection as used by substation workers. Because while it may be safe most of the time, that one in a million incident could be life changing. If you enjoy these videos you can help support the channel with a dollar for coffee, cookies and random gadgets for disassembly at:- http://www.bigclive.com/coffee.htm This also keeps the channel independent of YouTube's advertising algorithms allowing it to be a bit more dangerous and naughty. #ElectronicsCreators

Comments

Paul Schuur

I watched it (partly) in German - just for the fun of it. Unfortunately no Dutch translation.

Big Clive

Probably because so many Dutch are fluent in English. How was the quality of the German voiceover?

Kieran Kennedy

Surely there should have been an OMP moment between the first part & back at the bench?

clownhands

Hey Clive, where does the carbon that constitutes electrical shit stains actually come from? Is it the plastic insulation of conductors?

Big Clive

It's usually degradation of the materials, triggered by water or contaminants on the surface that allow a current path over the surface.

Brian Deschene

My late stepfather worked as industrial electrician. He told of a log that was kept in each panel when a breaker was reset. This allowed tracking (no pun intended) between different personnel/shifts of problematic circuit and/or breaker. If a breaker was reset “some number” of times (ten?), it was preventatively replaced. This avoided becoming slowly damaged by successive arcing internally. Don’t know if this would avoid cascade failure described here or not.

Paul Schuur

It was OK for me, but I'm not a fluent German speaker. It was still quite robotic though.

Kai-Steffen Hielscher

For me as a native German speaker, there were some problems. The translations got some techincal terms right, like "Kriechstrom" for "tracking", impressive. But it alters the meaning at some points. For example, at 1:19 the translation says that the resistance keeps increasing over time, so the complete opposite of what is happening and what Clive mentioned.

Kai-Steffen Hielscher

But it did not get all the terms right: Sometimes, "Leistungsschalter" (high-power switch) for "breaker". The correct term would be "Leitungsschutzschalter". Or "bio-metal" instead of "bimetal". The biggest problem is that the German version is absolutely no fun to watch, boring and dull at best, even confusing and wrong at some points.

Paul Schuur

I totally agree. Clive's voice and vocabulary is perhaps more important than the content itself.

Big Clive

I had to correct the autodetected word to tracking. I would guess that people will be aware that the video has been auto-dubbed and use the audio more as an interpretation of what's happening on screen.

Big Clive

That's actually a good thing. It would reduce the likelihood of this issue occurring.

Kai-Steffen Hielscher

Could be, but I am not sure they would watch them at all. Clive, your original videos have lots of entertainment value, the dubbed ones don't. By the way, "Leitungsschutzschalter" is the correct technical term for these circuit breakers, but most people here would just call them "Sicherung" (fuse) or "Sicherungsautomat" (automatic fuse). Not sure the general German population would even know what a "Leitungsschutzschalter" is.

Harris Chalk

Quite enjoy the failed protection device videos, it always interesting seeing inside after an incident has occurred.

Mark Gray

I just watched a technical video that had been machine translated German to English. There were a few incorrect words there too but it was mostly understandable. Machine translation has come a long way! Like all audio dubbed videos though, the experience is somewhat jarring, and the AI voice doesn't help.

Mike Page

The industrial end-user might appreciate a counter. But that'll never happen because no manufacturer would ever want to admit their product wears out. The manual tally makes most sense.

Mike Page

My son does conference media and the subcontract company promised subtitles but what they delivered was only 90% there. It's a royal PITA to get right ... but so important.