There's nothing WRONG with these testers.  This is just Fluke trying to avoid litigation from non-technicals who may not fully understand the tests that are being carried out and may have less tolerance to tingles than seasoned electricians.

On a plus note you do get to change the tester for a set of decent test lamps.

Files

Previews only

Why Fluke are recalling their SM100/200/300 plug-in testers.

Fluke are recalling their plug-in socket testers and offering exchange products. There's nothing actually wrong with the testers other than the modest current used to power the test indicators that can cause a strong sensation when a ground path is open circuit and someone bridges it during the test. (mild shock risk) The recall is more an indication of the increasingly litigious nature of society and the current trend of deskilling electricians so they don't fully understand the tests they are doing. This is epitomised by the profit motivated Part P system where a traditional 4 year (10,000 hour) mentored apprenticeship has been replaced by one week courses where everyone passes and gets electrically certified in return for ongoing cash payments to private companies. (That needs its own video.) If you have one of these testers you can return it to Fluke in exchange for a set of awesome test-lamps or the somewhat less desirable option of a padded bag and cheap non-contact live wire detector, which despite the quoted value is actually a much lesser prize. As you can probably guess, I strongly recommend Fluke's awesome test-lamps as being 100% suitable for industrial use and totally worthy of addition to your tool kit. If you enjoy these videos you can help support the channel with a dollar for coffee, cookies and random gadgets for disassembly at:- http://www.bigclive.com/coffee.htm This also keeps the channel independent of YouTube's advertising algorithms allowing it to be a bit more dangerous and naughty.

Comments

Anonymous

I saw that recall notice on the Screwfix website and thought it odd that Fluke would make something potentially dangerous.

Pixscotland

Oh. Random wee Fbomb at 15:30 that you might want to censor from TheTubes...

Anonymous

Thanks for the public service announcement. I have both the SM100 and its replacement T90 in my toolbox, so there is no benefit in replacing it, so I’ll be hanging onto it with caution. I do have a small moan about the T90, in that the impedance is low enough to trip the RCD if you put it between phase and earth (which is the same as would happen with a real test lamp).

Peter Argyropoulos

This is a great PSA for addressing a test scenario that most of us wouldn't give much thought to. I wouldn't think twice about testing a bad ground with a regular multimeter set to Low-Z if I were getting wonky readings in the non Low-Z setting which would cause the exact same danger to someone downstream who happened to get in contact with a conduit or whatever was bonded to the bad ground. It's certainly something to keep in mind. Thanks!

Gordo

Clive, this might be a daft question. The 10mA your meter registers between tester & earth would be relatively unaffected by your meter's resistance on the 200mA AC range. Wouldn't the resistance of your body be much higher? If I lick my fingers and squeeze my multimeter probes, the lowest resistance I can get is well over 100k. Even touching both probes onto my tongue isn't much lower. Is there some kind of effect whereby your body's resistance drops when current starts to flow, or your grip tightens from the muscle spasms. Or does the higher voltage promote a higher current. What thinks you?

Big Clive

These test lamps use a PTC style current limiter to allow a wide voltage range. If you use them between Live and Neutral first and then do the Live to Earth test they may not pass that initial high current pulse that trips the RCD.

Big Clive

Your body would have a resistance depending on the environment. But it would still be a lot of current in terms of the sensation of shock it produced. Hard dry skin has pretty impressive resistance, but if it's sweaty or abraded then that reduces. As soon as the insulation value breaks down higher current will flow.

Gordo

I've had enough shocks from 240V mains to know that it hurts, whether your hands are sweaty or not. It's made me more careful ;-)