A while ago John Ward featured a failed RCBO (Residual Current Breaker with Overload protection) which is like a combined overcurrent circuit breaker with additional earth/ground fault detection.  His had clearly failed with a bang, and so has this one.  But mine appears to have been louder.

Files

Previews only

Totally exploded Hager RCBO (RCD/GFI with overcurrent trip)

I've always pondered whether cramming the RCD/GFI circuitry into a breaker designed to break up to 10,000A of fault current was a compromise. It turns out it does open up the possibility of an internal flashover. My guess for the fault scenario that caused this is that the switching contacts welded shut allowing current to continue flowing, the electronic module tried to trip the welded mechanism, and then burned out initiating an arc that allowed the live to flash over to the neutral. John Ward featured a similar breaker failure. His video is here:- https://www.youtube.com/watch?v=TRUBlZCNo8U I'd suggest resetting these breakers with extreme caution if you believe there to have been a major fault condition that may still be present. The presence of the Live and Neutral connections in the same enclosure raises the risk of plasma/explosion hazards. If you enjoy these videos you can help support the channel with a dollar for coffee, cookies and random gadgets for disassembly at:- http://www.bigclive.com/coffee.htm This also keeps the channel independent of YouTube's advertising algorithms allowing it to be a bit more dangerous and naughty.

Comments

B3

Lightning?

Big Clive

I think it failed when switched on.

BB

High inrush is caused by capacitive loads not inductive :P Old school linear power supplies had this problem. Good video. Possible cause may have been due to the contacts welding and the protect circuit trying to disconnect a welded contact.

Chris Talbot

So... you're suggesting that an industrial AC induction motor won't have a high inrush current, and I can just specify the supply/breaker capacity and the cable to suit the nominal steady-state load without causing any issues...? Hmmmm...... I'm sure what you meant to say is that both highly capacitive loads AND highly inductive loads can cause large inrush currents at switch-on. ;) Welded contacts might have been a cause of failure, but given that the internal switch mechanisms of these MCBs/RCBOs are designed specifically to prevent that from happening, I'd say it's unlikely. Although I suppose if the load was pushing the limit of the breaker (but not quite high enough to cause a switch-on trip) it might be possible for the contacts to briefly arc over and weld together at switch-on, which would cause a catastrophic failure later when the device is tripped.

Anonymous

I learn about electrical safety from these videos. Power tool safety? Not so much. :P

Chris Talbot

Those lockout devices are neat, but a full kit for all the different breaker types isn't cheap, plus the need to keep suitable padlocks and all the keys for them can make them a little impractical. We generally still rely on the good old twist of wire through the holes with a lockout tag attached. The sight of yellow & black warning tags (and the very stiff penalties attached to unauthorised removal of same) are generally considered to be a sufficient deterrent for anyone tempted to mess around with the board.

Anonymous

What’s the blue cable fer?

Anonymous

I like JW's dry sense of humour.

Michael Thompson

I really enjoyed the breakdown of this unit (pardon the pun)

Benjamin Hall

Failed when switched on. Reminds me of a time long ago...walked into a building at work the morning after fierce electrical storms the night before. No power. Went to the panel, and the 480 VAC 3-phase main was tripped. Okay, turned on the main, all was well. Saw that the breaker for the surge arrestor was tripped. Reading the instructions on the surge arrestor - "if tripped, reset breaker." So we did that. As soon as that breaker made contact, KA-BOOM! Fire shot out from the sides of the panel! Turned it back off...and changed our undergarments... The electricians noted that some dumbass had jammed a three-phase delta arrestor into a Wye circuit when the building was built...

Chris Talbot

A mate of mine used to work on large (>1000A/phase) ventilation motors during a local motorway construction project. They were having issues water leaks in a particular segment of the tunnel. Some poor bastard went in to reset a 50kVA supply breaker after a switch room had flooded and the bloody thing just vaporised itself, along with two 10mm thick copper bussbars and most of the other equipment in the cabinet.... the supply authority hadn't isolated the supply at the submain transformer, for some reason, but the foreman had said it was already made safe so he didn't bring his test lamps. The guy survived, barely... he lost sight in one eye due to the flash and had some very nasty burns. Several companies copped some pretty severe fines after the incident apparently. This kind of equipment is manufactured to a very high standard, but it can never withstand the combined forces of human error and physics. Not To Be Messed With.